UPS Runtime Configuration
50KVA UPS — 4-hour backup configuration

Matching UPS
Emerson Adapt-PM-50KVA-250K frame
Plan 1Long machine 50KVA 4 hour hour configuration scheme Y = 417
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- Emerson Adapt-PM-50KVA-250K Framework
- Emerson
- 1
- 1*450.00kg
- 1000*1000*2000mm
- 230,947.00
- 230,947.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- 4 groups 160 block
- 160*30.50kg
- 330*171*214mm
- 1,638.00
- 262,080.00
- battery cabinet:
- RC40
- Ruiwu
- 4 groups
- 4*0.00kg
- 0*0*0mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- No matching battery cable
- 161 root
- 161*0kg
- Standard
- 0.00
- 0.00
- DC air on:
- No matching DC open
- 5 groups
- 0kg
- 5*mm
- 0.00
- 0.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 2500.00
- 1 unit
- 2,500.00
- Battery installation fee
- 20.00
- 160 only
- 5,700.00
- Logistics transportation fee
- 2715.00
- 2715.00
- In-place fee
- 5530.00
- 5530.00
Total: 5,330.00kg 506,972.00.00Scenario Download (Execl)Submit order
Installation parameters
50KVA input AC 380V: output AC 380V
| Input parameter | |
| Input voltage | 220V AC |
| Input live conductor size | 25mm2 |
| Input neutral conductor size | 50mm2 |
| Input earth conductor size | 25mm2 |
| Input breaker | 150a -Input AC 380V: Output AC 380V |
| Output parameter | |
| Output voltage | 220V AC |
| Output conductor size | 25mm2 |
| Output neutral conductor size | 50mm2 |
| Output earth conductor size | 25mm2 |
| Output breaker | 150a -Input AC 380V: Output AC 380V |
| Battery specifications | |
| External battery breaker | 300A-Input AC 380V: Output AC 380V |
| External battery cable size | 50mm2 |