Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

30KVA UPS — 2-hour backup configuration

Rated power
30KVA
Backup time
2 h
Kehua YTR3330

Matching UPS

Kehua YTR3330

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 30KVA 2 hour configuration scheme Y = 312
  • Host:Kehua YTR3330
  • Empty opening:NSX100F_DC_3P_100A

    Number of: 4

    Battery DC switch cabinet
  • battery cabinet:RC16

    Quantity: 3
    Battery:Ruiwu RW-G-12-100

    Quantity: 3 groups of 48 blocks
    Connection line:25 square battery connection line

    Number of: 49
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Host:
  • Kehua YTR3330
  • Kehua UPS power supply
  • 1
  • 1*120.00kg
  • 320*840*867mm
  • 32,102.00
  • 32,102.00
  • Battery:
  • Ruiwu RW-G-12-100
  • Ruiwu
  • Group 3    48 blocks
  • 48*30.50kg
  • 330*171*214mm
  • 1,638.00
  • 78,624.00
  • battery cabinet:
  • RC16
  • Ruiwu
  • Group 3
  • 3*0.00kg
  • 828*499*1112mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 2500.00
  • 1 unit
  • 2,500.00
  • Battery installation fee
  • 20.00
  • 48.
  • 3,460.00

Total: 1,590.40kg 116,821.00.00Scenario Download (Execl)Submit order

Installation parameters

30KVA input AC 380V: output AC 380V
Input parameter
Input voltage 380V AC
Input live conductor size 10mm2
Input neutral conductor size 16mm2
Input earth conductor size 16mm2
Input breaker 63A -3P
Output parameter
Output voltage 380V AC
Output conductor size 10mm2
Output neutral conductor size 16mm2
Output earth conductor size 16mm2
Output breaker 63A-3P
Battery specifications
External battery breaker 150A-3P