UPS Runtime Configuration
5KVA UPS — 8-hour backup configuration

Matching UPS
APC SU5000UXICH
Plan 1Long machine 5KVA 8 hour hour configuration scheme Y = 833
- Main component
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Host:
- APC SU5000UXICH
- APC (Schneider Electric)
- 1
- 1*71.36kg
- 439*229*665mm
- 9,306.00
- 9,306.00
- Battery:
- Ruiwu RW-G-12-100
- Ruiwu
- Group 9 36 pieces
- 36*30.50kg
- 330*171*214mm
- 1,638.00
- 58,968.00
- battery cabinet:
- RC4
- Ruiwu
- Group 9
- 9*0.00kg
- 499*499*572mm
- 0.00
- 0.00
- Battery switch box
- Model
- Brand
- Quantity
- Weight
- Dimensions
- Unit price (RMB)
- Subtotal (Yuan)
- Connection line:
- 6 square battery connection line
- Ruiwu
- 37
- 37*0.00kg
- Standard
- 6.00
- 222.00
- Service
- Service Name
- Unit price
- Quantity
- Subtotal (Yuan)
- Installation and transportation costs:
- Host installation fee
- 1000.00
- 1 unit
- 1,000.00
- Battery installation fee
- 20.00
- 36.
- 1,720.00
- Logistics transportation fee
- 641.00
- 641.00
- In-place fee
- 1381.00
- 1381.00
Total: 1,181.36kg 72,238.00.00Scenario Download (Execl)Submit order
Installation parameters
5KVA AC 220V input: AC 220V output
| Input parameter | |
| Input voltage | 220V AC |
| Input live conductor size | 4mm2 |
| Input neutral conductor size | 4mm2 |
| Input earth conductor size | 4mm2 |
| Input breaker | 32A -2P |
| Output parameter | |
| Output voltage | 220V AC |
| Output conductor size | 4mm2 |
| Output neutral conductor size | 4mm2 |
| Output earth conductor size | 4mm2 |
| Output breaker | 32A -2P |
| Battery specifications | |
| External battery breaker | 75A-2P |
| External battery cable size | 6mm2 |