Uninterruptible Power & Data-Centre Distribution Solutions

UPS Runtime Configuration

8KVA UPS — 8-hour backup configuration

Rated power
8KVA
Backup time
8 h
APC SURT8000UXICH

Matching UPS

APC SURT8000UXICH

Other backup times30 min1 h2 h4 h8 h
Plan 1Long machine 8KVA 8 hour hour configuration scheme Y = 167
  • Host:APC SURT8000UXICH
  • Empty opening:NSX100F_DC_2P_32A

    Quantity: 1

    Battery DC switch cabinet
  • battery cabinet:RC32

    Quantity: 1
    Battery:Ruiwu RW-G-12-100

    Quantity: 1 group of 32 pieces
    Connection line:6 square battery connection line

    Number of: 33
  • Main component
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)
  • Host:
  • APC SURT8000UXICH
  • APC (Schneider Electric)
  • 1
  • 1*41.82kg
  • 440*263*723mm
  • 18,255.00
  • 18,255.00
  • Battery:
  • Ruiwu RW-G-12-100
  • Ruiwu
  • Group 1    32 blocks
  • 32*30.50kg
  • 330*171*214mm
  • 1,638.00
  • 52,416.00
  • battery cabinet:
  • RC32
  • Ruiwu
  • Group 1
  • 1*0.00kg
  • 828*974*1112mm
  • 0.00
  • 0.00

  • Battery switch box
  • Model
  • Brand
  • Quantity
  • Weight
  • Dimensions
  • Unit price (RMB)
  • Subtotal (Yuan)

  • Service
  • Service Name
  • Unit price
  • Quantity
  • Subtotal (Yuan)
  • Installation and transportation costs:
  • Host installation fee
  • 1000.00
  • 1 unit
  • 1,000.00
  • Battery installation fee
  • 20.00
  • 32.
  • 1,640.00

Total: 1,019.02kg 74,288.00.00Scenario Download (Execl)Submit order

Installation parameters

8KVA AC 220V input: AC 220V output (1 to 1)
Input parameter
Input voltage 220V AC
Input live conductor size 6mm2
Input neutral conductor size 6mm2
Input earth conductor size 6mm2
Input breaker 40A -2P
Output parameter
Output voltage 220V AC
Output conductor size 6mm2
Output neutral conductor size 6mm2
Output earth conductor size 6mm2
Output breaker 40A -2P
Battery specifications
External battery breaker 100A-2P
External battery cable size 10mm2

8KVA input AC 380V: output AC 220V(3 to 1)
Input parameter
Input voltage 220V AC
Input live conductor size 6mm2
Input neutral conductor size 6mm2
Input earth conductor size 6mm2
Input breaker 40A -2P
Output parameter
Output voltage 220V AC
Output conductor size 6mm2
Output neutral conductor size 6mm2
Output earth conductor size 6mm2
Output breaker 40A -2P
Battery specifications
External battery breaker 100A-2P
External battery cable size 10mm2

8KVA input AC 380V: output AC 380V(3 to 3)
Input parameter
Input voltage 220V AC
Input live conductor size 6mm2
Input neutral conductor size 6mm2
Input earth conductor size 6mm2
Input breaker 40A -Input AC 380V: Output AC 380V
Output parameter
Output voltage 220V AC
Output conductor size 6mm2
Output neutral conductor size 6mm2
Output earth conductor size 6mm2
Output breaker 40A -Input AC 380V: Output AC 380V
Battery specifications
External battery breaker 100A-Input AC 380V: Output AC 380V
External battery cable size 10mm2